From a59524a49f2a7ce0de28ce13577be110e0c62bb1 Mon Sep 17 00:00:00 2001 From: psy <psy@darmstadt.ccc.de> Date: Wed, 9 Aug 2023 12:06:21 +0200 Subject: [PATCH] remove 4mm for 32a --- docs/facilities.md | 2 +- 1 file changed, 1 insertion(+), 1 deletion(-) diff --git a/docs/facilities.md b/docs/facilities.md index 818f1c4..0571e24 100644 --- a/docs/facilities.md +++ b/docs/facilities.md @@ -245,7 +245,7 @@ Make sure to use cables with adequate wire cross section: * Use at least 1.5 mm² for 16 Amp singlephase (Schuko connector) * Use at least 2.5 mm² for 16 Amp triphase (CEE 16A connector) -* Use at least 4 mm², better 6 mm² for 32 Amp triphase (CEE 32A connector) +* Use at least 6 mm² for 32 Amp triphase (CEE 32A connector) Always use CEE connectors for triphase cables. -- GitLab