@@ -245,7 +245,7 @@ Make sure to use cables with adequate wire cross section:
* Use at least 1.5 mm² for 16 Amp singlephase (Schuko connector)
* Use at least 2.5 mm² for 16 Amp triphase (CEE 16A connector)
* Use at least 4 mm², better 6 mm² for 32 Amp triphase (CEE 32A connector)
* Use at least 6 mm² for 32 Amp triphase (CEE 32A connector)
Always use CEE connectors for triphase cables.